How Texture estimates transformer loading

Read an hourly estimate, trace a peak and interpret gaps in meter coverage

A transformer can carry power in either direction. Import supplies local demand. Export sends power back toward the grid. Texture estimates both from hourly meter energy. A transformer can reach its highest loading during an export hour.

From meter readings to estimated kVA#

  1. Texture uses grid topology to associate consumer service meters with a transformer or transformer bank. It selects one hourly reading per consumer and energy register.
  2. Texture adds the selected import readings and subtracts the selected export readings for that same hour. The result is net energy in kWh. At a service with solar behind the billing meter, the billing meter measures energy exchanged with the grid. A separate production meter can also record energy used on site.
  3. Dividing net kWh by one hour gives average net kW. Dividing by the assumed power factor gives estimated signed kVA. The current assumption is 0.95. Positive means import, negative means export.
  4. The peak kVA for a window is the largest magnitude among its eligible hours. Peak utilization is 100 × peak kVA ÷ nameplate kVA. A missing or placeholder rating leaves utilization unavailable. Peak kVA can still be shown.

For example, suppose the meters report 3 kWh of import and 22 kWh of export in the same hour. The result is −19 kWh, or −19 kW on average. At a power factor of 0.95, that hour plots at −20 kVA and contributes a 20 kVA magnitude toward the peak. On a 25 kVA transformer, that is 80% of its rating.

Reading the different views#

View or valueWhat it tells you
Hourly Net and Loading charts with loading analytics enabledNet shows signed average kW. Loading shows that flow in estimated signed kVA. A bank uses the meters assigned to the bank.
Daily point on those chartsThe point averages the signed values from eligible hours in the bucket. Import and export can cancel. Where a range is shown, its ends mark the lowest and highest eligible hourly values.
Fleet table, detail loading metrics, exports and agent loading summariesPeak kVA is the largest eligible hourly magnitude within the selected rolling window. Peak export kVA reports the largest export magnitude. The peak hour and its direction identify the point to inspect on the chart.
Saved boards with Net, consumption and generation on one chartThe traces share hourly or daily buckets for comparison. The separate Consumption / Generation view can show finer readings when the meters report them.
Agent time-series chartsWhere loading analytics is available, ask for hourly or daily signed net kW or estimated kVA for a transformer or bank. Each chart shows one metric, and a daily average uses only eligible hours.
Mobile Explore loading filtersFilters use published utilization for the selected rolling window.
Percent of time above ratingThe number of eligible hours above the recorded rating divided by the number of eligible hours, expressed as a percentage.
Explore hourly map and loading alertsThe hourly map shows an individual hour. A loading alert evaluates eligible hours against its configured threshold and duration.

To check a peak, match the transformer or bank, the peak hour and the reporting window. Use the hourly chart value, or the relevant end of the daily range where it is shown. A daily average can be small even on a day with a large export peak.

The rankings reflect the readings available when that window was published. The chart reads the current hourly history for the requested dates. A corrected reading can reach the chart before the next ranking refresh. Even when both views show the same latest source hour, the underlying values can have been revised.

Coverage and measurement limits#

An eligible hour requires the current meter roster to match and every expected consumer to report import energy, with unambiguous membership. An import reading of zero still counts as a report. Some meters send export readings only when export is positive. An absent export reading therefore does not, on its own, establish whether a site has generation.

An hour with incomplete readings has no loading value. A day with four eligible hours averages those four values. A day with no eligible hours has no point. The source timestamp marks the start of the latest stored hour matching the roster, even if that hour was incomplete. Check the eligible-hour count when comparing windows.

When two meters report the same register for one service in the same hour, Texture uses the reading from the device record created most recently in Texture. The calculation does not check the utility’s changeout date. If the retired meter still reports and its device record was added later, its reading can displace the replacement meter’s reading for that hour.

The current roster is based on consumer service connections. A separately metered generator with its own grid connection can be missing from this estimate. A generation meter's production total alone cannot establish where it connects. Consumption and Generation series are useful for inspecting individual meter roles. A sum across those meters can include both billing and production readings for the same installation.

Estimated kVA reflects hourly average real power and an assumed power factor. Shorter peaks, reactive-power variations, phase imbalance and transformer temperature require other measurements.